Zy-a038 Three-phase handheld electrical inspection instrument (Grade 0.5)

Add time:2022-04-18   Number of views:297  

An overview,

The two-way station branch identification instrument produced by our company is a high-precision testing instrument that integrates the functions of station user identification, line branch identification, electrical independence testing between stations, basic electrical parameters testing, voltage and current harmonic content measurement and so on. The instrument adopts the current industry advanced technology and special zero frequency carrier pulse current emission and detection technology, can effectively guarantee the measuring radius is enough to cover all kinds of power supply area users accurate identification of the distance, there is no more than one variable short of high-pressure situations crosstalk, power carrier transmission distance close, affected by the load is large, a total of cable interference, etc.; The recognition success rate can reach 100 percent.

Two, technical indicators

1. Test section of the platform area

Communication mode: special load signal transmission, distance: ≥5km

Current test distance: ≥5km

Identification period: ≤6 seconds

Test success rate: 100%

Number of branch identification: 3 channels for a single host (18 channels can be extended in multi-host mode)

Clamp type current transformer: 750A/1500A flexible current transformer

50mm calipers (50A/100A/250A/500A) (optional)

2. Measurement of electrical parameters

Voltage: ±0.2% Current: ±0.5%

Power: ±0.5% Frequency: ±0.02Hz

Phase: + / - 0.2 °

3. Power quality

Voltage harmonic measurement times: 2-51

Current harmonic measurement times: 2-51

Measurement error of harmonic voltage content: ≤ 0.1%

Measurement error of harmonic current content: ≤ 0.2%

4. Work environment

Working environment temperature: -30℃~60℃

Working environment humidity: ≤95%RH

Working voltage: AC220V±10%

5, insulation

(1) The insulation resistance of voltage and current input terminal to the casing is more than 100M ω.

(2) The input end of the working power supply is subjected to power frequency 1.5kV (effective value) between the shell, and the experiment lasts for 1 minute.

6, weight,

Weight: 1 kg

7, single machine volume

Size: 25 cm * 16 cm * 6 cm