Welcome to visit Baoding Zhuoyue Electric Co.,LTD.!
switch 中文  |   switch English
Hotline:
+86-312-3136236/3021783
Your location:Home > Product > Secondary protection
Secondary protection

Zyx-q first harmonic elimination

Add time:2022-04-18   Number of views:391  

I. Overview

ZYX-Q harmonic eliminator is a high capacity nonlinear resistor installed between the neutral point of primary side and ground of electromagnetic voltage transformer, which plays the role of damping and current limiting. It can effectively restrain the ferromagnetic resonance of PT and protect the PT and the high-voltage fuse on the primary side of PT from being damaged.

Table of AC electrical parameters of harmonic eliminator body

Serial number

Project

Technical index

Type ZYX-Q-10 (6)

Type ZYX-Q (D)-10 (6)

Model ZYX-Q-35

Type ZYX-Q (D)-35

1

Voltage and resistance of harmonic eliminator passing through AC 0.5 mA (peak current)

RosmAp

(V, peak value/tick 2)

180

30

180

30

600

80

600

80

RosmAp (K Ω)

> 420

> 420

> 1450

> 1450

2

Voltage and Resistance of Harmonic Eliminator Passing AC 5mA (Peak Current)

RosmAp

(V, peak value/tick 2)

550

100

550

100

1600

200

1600

200

RosmAp (K Ω)

> 120

> 120

> 400

> 400

3

Whether to limit the power frequency voltage across the harmonic eliminator

Unlimited

Limit below 3kV (peak/)

Unlimited

Limit below 5kV (peak/)

4

Power

800 W

1000 W

5

Heat capacity

500mA for 10 minutes